Error Conditions of the Red Diagnostics Light 1Hz – Error in Configuration Indicates that the I/O length variable set during initialization is not equal to the length set during configuration of the network. See Configuring the Slave Device on page 14 for lengths supported by the SmartLinx module, and see your PLC documentation for setting the I/O length variable. 2Hz – Error in User Parameter Data Indicates that the length and / or contents of the user parameter data set during initialization of the module is greater than the length and/or contents set during configuration of the network. See Configuring the Slave Device on page 14 for supported lengths.
4Hz – Error in Initialization Consult your Siemens Milltronics representative. Operation LED EnviroRanger ERS 500, Milltronics BW500, Milltronics BW500/L, Milltronics SF500, MultiRanger 100/200, HydroRanger 200 LED • blinks orange as the module is initialized • blinks green during normal operation Operation Page 12 SmartLinx PROFIBUS DP – INSTRUCTION MANUAL 7ML19981AQ03