DeviceNet Slave Communication Module IFD9502 z Common Services 5. Class 0x05 Connection z Class attributes z Instance 1: Master/Slave Explicit Message Connection z Instance 2:

Polled I/O Connection DVP-PLC Application Manual 29 Attribute ID Access rule Name Data type 3 Get/Set BusofInterrupt BOOL 4 Get/Set BusofCounter USINT 5 Get AllocationInfo AllocationChioce MasterNodeAddress BYTE USINT 6 Get MACIDSwitchChanged BOOL 7 Get BaudRateSwitchChanged BOOL 8 Get MACIDSwitchValue USINT 9 Get BaudRateSwitchValue USINT Service code Implemented for Service name Class Instance 0x0E Yes Yes Get Attribute Single _ _ 0x10 No Yes Set Attribute Single _ _ 0x4B No Yes Allocate Master/Slave Connection Set _ _ _ 0x4C No Yes Release Master/Slave Connection Set _ _ _ Attribute ID Access rule Name Data type 1 Get Revision UINT Attribute ID Access rule Name Data type 1 Get State USINT 2 Get InstanceType USINT 3 Get TransportClassTrigger USINT 4 Get ProducedConnectionId UINT 5 Get ConsumedConnectionId UINT 6 Get InitialCommCharacteristics BYTE 7 Get ProducedConnectionSize UINT 8 Get ConsumedConnectionSize UINT 9 Get/Set ExpectedPackedRate UINT 12 Get/Set WatchdogTimeoutAction USINT 13 Get Produced Connection Path Length USINT 14 Get Produced Connection Path EPATH 15 Get Consumed Connection Path Length USINT 16 Get Consumed Connection Path EPATH