Schneider Electric — Electrical Characteristics

Altivar 16 AC Drive Specifications 4 Environment Standards UL, CSA, IEC, VDE, CE Degree of protection NEMA 1, IP30 IP30 without the top plate mounted Resistance to vibration and shocks Conforming to IEC 68-2-6:

- 2 mm peak to peak from 5 to 16 Hz - 1 g peak up to 150 Hz Maximum ambient pollution Pollution degree 2 according to IEC 664 Maximum relative humidity 93 % non-condensing without dripping Temperature Storage Operation °F (°C) - 13 to +158 (-25 to +70) °F (°C) +32 to +104 (0 to +40) with NEMA 1 °F (°C) +32 to +122 (0 to +50) with IP30 Maximum altitude ft (m) 3300 (1000) without derating Derate by 3 % for each additional 3300 ft (1000 m) Electrical characteristics Altivar ATV16 U09M2 U18M2 U29M2 U41M2 U18N4 U29N4 U41N4 U54N4 U72N4 Total dissipated power at rated load W 22 35 55 65 35 50 70 100 135 Input Voltage Frequency V 208 - 10 % to 240 + 10 % 400 - 15 % to 460 + 15 % Hz 50/60 ± 2 50/60 ± 2 Output voltage Maximum voltage equal to input voltage Output frequency range Hz 0.1 to 50/60 Hz 0.1 to 200/400 with option Transient overtorque 150 % of rated motor torque (typical value) Starting torque 200 % of rated motor torque for 0.2 s Braking torque 30 % of nominal motor torque (typical value) Up to 150 % with option