Certificate No. 24-192-01 Certificate Applicant: Victron Energy B.V. De Paal 35 1351 JG Almere Netherlands Product: Battery Inverter with integrated automatic disconnection device between a generator and the public low-voltage grid Intended use: Battery Inverter with an automatic disconnection device with single phase mains surveillance in accordance with Engineering Recommendation G99-1 for photovoltaic systems with a single phase parallel coupling via an inverter to the public mains supply. The automatic disconnection device is an integral part of the aforementioned inverter. Applied standards and guidelines: SOP-9-1_15 GCC Certification Program, 09/21 Based on:

Engineering Recommendation G99 Issue 1 – Amendment 10; 04 March 2024 Requirements for the connection of generation equipment in parallel with public distribution networks on or after 27 April 2019 The safety concept of an aforementioned representative product corresponds at the time of issue of this certificate to the valid safety specifications for the specified use in accordance with regulations. The units are only compliant with type A Power Generating Module requirements. TC_G99-1 Amendment 10_type A inverter connected power generating modules_eng _A Report No: 17PP264-48_1 Date of issue: 2026-01-15 Kiwa Primara GmbH GewerbestraЯe 28 - 32 87600 Kaufbeuren Germany Tel.

+49 8341 99726-0 primara@kiwa.com www.kiwa.de Tanja Rottach - Digitally signed | see http://ca.kiwa-deutschland.de for more details - Tanja Rottach Certification Engineer Page 1 of 16 Model: MultiPlus-II 48/3000/35-32 230V, MultiPlus-II 48/3000/35-32 230V GX MultiPlus-II 48/5000/70-50 230V, MultiPlus-II 48/5000/70-50 230V GX MultiPlus-II 24/3000/70-32 230V, MultiPlus-II 24/3000/70-32 230V GX Rating: Output power (feed in on-grid): 2,5kVA / 2,47kW 4,5kVA / 4,4kW 2,5kVA / 2,47kW Model: MultiPlus-II 48/4k5/55-32 230V, MultiPlus-II 48/4k5/55-32 230V GX MultiPlus-II 48/6k5/100-50 230V, MultiPlus-II 48/6k5/100-50 230V GX Rating: Output power (feed in on-grid): 4,0kVA / 4,0kW 6,0kVA / 6,0kW

Стр. 1

Certificate 24-192-01 Page 2 of 16 Annex to certificate Test 1 - Frequency, Voltage, active power over time diagram Operating Range: MultiPlus-II 48/6k5/100-50 230V GX U [V] f [Hz] Cos φ P [kW] Limit [%Sn]:

Test 1 85%Un 195,5V 47,00Hz 1,00 Registered Capacity - Measured 20s avg 195,5V 47,00Hz 1,00 6,0 Y Test 2 85%Un 195,5V 47,50Hz 1,00 Registered Capacity - Measured 90min avg 195,5V 47,50Hz 1,00 6,0 Y Test 3 110%Un 253V 51,50Hz 1,00 Registered Capacity - Measured 90min avg 253V 51,50Hz 1,00 6,0 Y Test 4 110%Un 253V 52,00Hz 1,00 Registered Capacity - Measured 15min avg 253V 52,00Hz 1,00 6,0 Y Test 5 100%Un 230V 50,00Hz 1,00 Registered Capacity - Measured 90min avg 230V 50,00Hz 1,00 6,0 Y Test 6 Start frequency Change End frequency Confirm no trip Positive frequency drift 49,5Hz +1,0Hz/sec 50,0Hz No trip Negative frequency drift 50,5Hz -1,0Hz/sec 50,0Hz No trip

Стр. 2

Certificate 24-192-01 Page 4 of 16 Annex to certificate Test 4 - Frequency, Voltage, active power over time diagram Test 5 - Frequency, Voltage, active power over time diagram Note: The overfrequency derating function and the interface protection has been deactivated for this test

Стр. 4

Certificate 24-192-01 Page 5 of 16 Annex to certificate Power Quality – Harmonics MultiPlus-II 48/3000/35-32 230V Generating Unit tested to BS EN 61000-3-12 Generating Unit rating per phase (rpp) 2,47 kVA Harmonics % =Measured Value (Amps) x 23/rating per phase (kVA) Harmonic At 45-55% of rated output Limit in BS EN 61000-3-12 Measured Value (A) Measured Value (%) 1 phase 3 phase L1 L2 L3 L1 L2 L3 2 0,067 - - 0,628 - - 8% 8% 3 0,076 - - 0,707 - - 21,6% Not stated 4 0,058 - - 0,538 - - 4% 4% 5 0,154 - - 1,435 - - 10,7% 10,7% 6 0,039 - - 0,359 - - 2,67% 2,67% 7 0,112 - - 1,046 - - 7,2% 7,2% 8 0,024 - - 0,219 - - 2% 2% 9 0,063 - - 0,588 - - 3,8% Not stated 10 0,014 - - 0,130 - - 1,6% 1,6% 11 0,054 - - 0,498 - - 3,1% 3,1% 12 0,009 - - 0,080 - - 1,33% 1,33% 13 0,036 - - 0,339 - - 2% 2% THD - - - 2,408 - - 23% 13% PWHD - - - 3,735 - - 23% 22% Harmonic At 100% of Registered Capacity Limit in BS EN 61000-3-12 Measured Value (A) Measured Value (%) 1 phase 3 phase L1 L2 L3 L1 L2 L3 2 0,044 - - 0,409 - - 8% 8% 3 0,077 - - 0,717 - - 21,6% Not stated 4 0,040 - - 0,369 - - 4% 4% 5 0,083 - - 0,777 - - 10,7% 10,7% 6 0,027 - - 0,249 - - 2,67% 2,67% 7 0,054 - - 0,498 - - 7,2% 7,2% 8 0,016 - - 0,149 - - 2% 2% 9 0,043 - - 0,399 - - 3,8% Not stated 10 0,010 - - 0,090 - - 1,6% 1,6% 11 0,026 - - 0,239 - - 3,1% 3,1% 12 0,005 - - 0,050 - - 1,33% 1,33% 13 0,014 - - 0,130 - - 2% 2% THD - - - 1,459 - - 23% 13% PWHD - - - 1,744 - - 23% 22%