Delta — 4.3 I/O Mapping Table (as master mode)

DeviceNet Network Scanner DVPDNET-SL 4.2 Data Mapping Areas mapping relation is unchanged and user has no right to revise this area. The data mapping introduced in this chapter is the data mapping between PLC MPU and DVPDNET-SL. The Max 8 PLC DVPDNET-SL modules can be connected to PLC’s left side. After all DVPDNET-SL are connected to DVP-SV, DVP-SV will distribute data mapping areas to every DVPDNET-SL. The index of DVPDNET-SL is its unit number. The first DVPDNET-SL on the left hand side of DVP-SV is No. 1, the following DVPDNET-SL modules are No. 2, No. 3, No. 4 and so on. 4.3 I/O Mapping Table (as master mode) As DVPDNET-SL of unit No.

1 serves as master mode, the data mapping areas are distributed as below table.

DVP-PLC Operation Manual 12 DVPDNET DVPDNET DVPDNET DVPDNET DVPDNET DVPDNET DVPDNET DVPDNET DVP28SV RUN STOP DVPDNET-SL Mapped D registers index Output mapping Input mapping 1 D6250 ~ D6497 D6000 ~ D6247 2 D6750 ~ D6997 D6500 ~ D6747 3 D7250 ~ D7497 D7000 ~ D7247 4 D7750 ~ D7997 D7500 ~ D7747 5 D8250 ~ D8497 D8000 ~ D8247 6 D8750 ~ D8997 D8500 ~ D8747 7 D9250 ~ D9497 D9000 ~ D9247 8 D9750 ~ D9997 D9500 ~ D9747 Output mapping area Input mapping area D register Mapping area D ata length D register Mapping area Data length D6250 ~ D6281 Explicit message 3 program request 2 words D6000 ~ D6031 Explicit message program response 32 words D6282 ~ D6285 Bit-strobe command 4 words D6032 ~ D6035 Status of nodes in the scan list 4 words D6286 Reserved 1word D6036 DVPDNET-SL status 1 word D6287 ~ D6476 DeviceNet output 1 data 90 words D6037 ~ D6226 DeviceNet input data 190 words D6477 ~ D6497 Reserved 2 1 words D6227 ~ D6247 Reserved 21 words