DeviceNet Network Scanner DVPDNET-SL 4) Application example (I) 1> The connection DVPDNET DVP28SV RU N STOP Node Address:00 DeviceNet Node Address:02 Note: IFD9502, a Delta DeviceNet slave module can connect VFD AC motor drive to DeviceNet network. 2> Compulsory settings and explanations on devices „ Compulsory settings in DVPDNET-SL „ Compulsory settings in DNA02 „ Compulsory settings in VFD-B DVP-PLC Operation Manual 17 Target When M0 = On, read Class 1>>Instance 1>>Attribute 1 of IFD9502 Parameter Set value Explanation Node address 00 Set the node address of DVPDNET-SL to “00”. Baud rate 500kbps Set the communication speed of DVPDNET-SL and bus to “500kbps”.
Parameter Set value Explanation Node address 02 Set the node address of DNA02 to “02". Baud rate 500kbps Set the communication speed of DNA02 and bus to “500kbps”. Parameter Set value Explanation 02-00 04 The main frequency is operated on RS-485 interface. 02-01 03 The operation commands are operated on the communication interface. Operation by keys is valid. 09-00 01 Communication address of VFD-B: 01 09-01 03 Baud rate: 38,400 09-04 03 Modbus RTU mode. Data format