EM500 Open-Loop Vector Control Inverter User Manual 179 13 Preset Speed Terminal 3 0 0 0 1 Preset Speed 1 (F08.00) 0 0 1 0 Preset Speed 2 (F08.01) 0 0 1 1 Preset Speed 3 (F08.02) 0 1 0 0 Preset Speed 4 (F08.03) 0 1 0 1 Preset Speed 5 (F08.04) 0 1 1 0 Preset Speed 6 (F08.05) 14 Preset Speed Terminal 4 0 1 1 1 Preset Speed 7 (F08.06) 1 0 0 0 Preset Speed 8 (F08.07) 1 0 0 1 Preset Speed 9 (F08.08) 1 0 1 0 Preset Speed 10 (F08.09) 1 0 1 1 Preset Speed 11 (F08.10) 1 1 0 0 Preset Speed 12 (F08.11) 1 1 0 1 Preset Speed 13 (F08.12) 1 1 1 0 Preset Speed 14 (F08.13) 1 1 1 1 Preset Speed 15 (F08.14) 15 Preset PID Terminal 1 With these two terminals, inverter can realize 4 preset PID settings.
See the table below (0/1: Present function terminal is disabled / enabled) or table 7-16. 16 15 Preset PID Setting 0 0 Determined by PID setting source (F09.00) 0 1 Preset PID Setting 1 (F09.32) 1 0 Preset PID Setting 2 (F09.33) 1 1 Preset PID Setting 3 (F09.34) 16 15 Preset PID Setting 16 Preset PID Terminal 2 0 0 Determined by PID setting source (F09.00) 0 1 Preset PID Setting 1 (F09.32) 1 0 Preset PID Setting 2 (F09.33) 1 1 Preset PID Setting 3 (F09.34) 17 Preset Torque Terminal 1 With these two terminals, inverter can realize 4 torque settings. See the table below (0/1: Present function terminal is disabled / enabled) or table 7-19.
18 17 Preset Torque Setting 0 0 Determined by the torque setting source (F13.01) 0 1 Preset Torque 1 (F13.03) 1 0 Preset Torque 2 (F13.04) 1 1 Preset Torque 3 (F13.05) 18 17 Preset Torque Setting 18 Preset Torque Terminal 2 0 0 Determined by the torque setting source (F13.01) 0 1 Preset Torque 1 (F13.03) 1 0 Preset Torque 2 (F13.04) 1 1 Preset Torque 3 (F13.05) 19 Acceleration/Decele ration Time Terminal 1 EM500 inverter has four groups of acceleration/deceleration terminals, each group having two input terminals for acceleration and deceleration. The setting of the combined code of the 4 terminals, and relevant functions determines present acceleration/deceleration time.
As stated in the following table: (0/1: Present function terminal disabled/enabled). See function