User Manual of EM730/EM730E Series Inverter The PID setting depends on the digital PID setting (F09.01), and the specific percentage is F09.01/F09.03 * 100.00%. F09.00=1:AI1 F09.00=2:AI2 For the details of AI1 to AI2, refer to the description of F00.04. For PID setting, the percentage is directly given, and the maximum output is 100.00%. F09.00=5: PULSE high-frequency pulse (X5) The set percentage of PID is directly dependent on the HDI (percentage). For the details of AI1-AI2 and X5, see the description of F00.04. When used as the PID setting, the percentage will directly turn the set value, and the maximum output is 100.00%. F09.00=6:
communication setting The percentage of PID setting depends directly on the communication (percentage). If the master-slave communication (F10.05=1) is enabled and the inverter works as the slave (F10.06=0), the specific setting percentage is “700FH (master-slave communication setting) * F10.08 (slave receiving proportional coefficient)”, and the 700FH data range is -100.00% to 100.00%, as detailed in Table 12-31. For the general communication (F10.05=0), the specific setting percentage is “7004H (communication setting of process PID setting)”, and the 7004H data range is -100.00% to 100.00%, as detailed in Table 12-31. F09.02=1:AI1 F09.02=2:
AI2 The PID feedback percentage is directly dependent on the AI (percentage). feedback, the percentage will directly turn the feedback value, and the maximum output is For the details of AI1 to AI2, see the description of F00.04. When is used as the PID 219 Function Default Function code name Parameter description Unit Attribute code setting F09.02 PID feedback source 1: AI1 2: AI2 3: retention 4: retention 5: PULSE, high-frequency pulse (X5) 6: Communication setting 1 〇