User’s Guide for EM760 series high-performance vector inverter 10 parameter copying. Protectio Protective Function Short circuit, overcurrent, overvoltage, undervoltage, phase loss, overload , n overheat, overspeed, load loss, external fault, etc.
Use condition s Location Indoor, at an altitude of less than 1 km, free of dust, corrosive gases and direc t sunlight Applicable -10℃ to +50℃, derating by 5% per 1℃ increase above 40℃, 20% to 90%R H environment (non-condensing) Vibration Less than 0.5g Storage environment -40℃~+70℃ Installation method Wall-mounted, floor-standing electrical control cabinet, through-wall Protection level Standard IP21/IP20 (remove the plastic cover at the top of the plastic case) Cooling method Forced air cooling