5.9 o: Operator Related Settings Note: 1. Refer to Defaults by Drive Capacity (o2-04) and ND/HD (C6-01) on page 183 for a list of o2-04 settings and parameters that change depending on the drive model selection. 2. Drive performance will suffer if the correct drive capacity is not set to o2-04, and protective functions will fail to operate properly. n o2-05: Frequency Reference Setting Method Selection Determines if the ENTER key must be used to input a frequency reference from the digital operator. Setting 0: ENTER Key Required Every change in the frequency reference setting on the digital operator has to be finalized by pressing the ENTER key before it becomes effective. Setting 1:
ENTER Key Not Required The output frequency changes immediately when the reference is changed by the UP and DOWN key on the digital operator. The ENTER key does not need to be pressed. The frequency reference is saved five seconds after the Up or DOWN key has been released. n o2-06: Operation Selection when LED Operator is Disconnected Determines if the drive will stop when an external LED operator (JVOP-182) is removed in LOCAL mode or with b1-02 set to 0. Setting 0: Continue Operation The operation is continued. Setting 1: Trigger a Fault The operation is stopped and an “oPr” fault is triggered. The motor coasts to stop. n o2-09:
Initialization Specification Selection This parameter sets the regional specifications for the drive and should not be changed. u o3: Copy Function Use o3 parameters to Read, Copy, and Verify the parameter settings to and from the drive using an LED operator (option). n o3-01 Copy Function Selection Parameter o3-01 selects the copy function operation. Parameter Details 0: No Action No action. 1: READ All parameters are copied from the drive to the LED operator. 5 2: WRITE All parameters are copied from the LED operator to the drive. 3: VERIFY Parameter settings in the drive are compared to those in the LED operator. Note:
When using the copy function, the drive model number (o2-04) and the software number (U1-14) must match or an error will occur. n o3-02 Copy Function READ Permission Parameter o3-02 can be used to prevent accidentally overwriting the data stored in the operator. SIEP C710606 33A OYMC AC Drive – J1000 User Manual 113 No. Name Setting Range Default o2-04 Drive Model Selection - Depending on drive size No. Name Setting Range Default o2-05 Frequency Reference Setting Method Selection 0 or 1 0 No. Name Setting Range Default o2-06 Digital Operator Disconnection Operation 0 or 1 0 No. Name Setting Range Default o3-01 Copy Function Selection 0 to 3 0 No.
Name Setting Range Default o3-02 Copy Function READ Permission 0, 1 0