Load Cell Module DVP02LC-SL CR#51: Error code Explanations: CR#52, 53 ,54, 55: Communication format for RS-232 and RS-485 Explanations: Example: If you would like to communication format for RS-232 to be “115200, 7, E, 1, ASCII” set CR#53 to “H’0400”. DVP-PLC Operation Manual 16 bit Status bit3 H’0008 CH2 exceeds max. weight (overload) bit4 H’0010 CH1 measured value is stable. bit5 H’0020 CH2 measured value is stable.
bit6 ~ 15 Reserved Bit Content Error Bit Content Error b0 K1 (H’0001) Power supply abnormality b1 K2 (H’0002) Hardware abnormality b2 K4 (H’0004) CH1 conversion error b3 K8 (H’0008) CH1 SEN voltage error b4 K16 (H’0010) CH2 conversion error b5 K32 (H’0020) CH2 SEN voltage error b6 ~ b15 K64 (H’0040) Reserved Note: Every error status is determined by its corresponding bit, so there might be more than 2 error statuses occurring at the same time. 0 refers to no error; 1 refers to error occurring.
bit15 bit14 ~ bit8 bit7 bit6 bit5 bit4 bit3 bit2 bit1 bit0 ACSII/RTU Reserved Baudrate Data length Stop bit Parity Description bit15 ACSII/RTU 0 ACSII 1 RTU bit7 ~ bit4 Baudrate 0 9,600 bps 1 19,200 bps 2 38,400 bps 3 57,600 bps 4 115,200 bps 5 Else none bit3 Data length (RTU = 8 bits) 0 7 1 8 bit2 Stop bit 0 1 bit 1 2 bits bit1 ~ bit0 Parity 0 Even 1 Odd 2 None 3 None