Mitsubishi FR-A800 — 2.3.1 Inverter installation environment

2.3 Installation of the inverter and enclosure design When designing or manufacturing an inverter enclosure, determine the structure, size, and device layout of the enclosure by fully considering the conditions such as heat generation of the contained devices and the operating environment. An inverter unit uses many semiconductor devices. To ensure higher reliability and long period of operation, operate the inverter in the ambient environment that completely satisfies the equipment specifications. 2.3.1 Inverter installation environment The following table lists the standard specifications of the inverter installation environment.

Using the inverter in an environment that does not satisfy the conditions deteriorates the performance, shortens the life, and causes a failure. Refer to the following points, and take adequate measures. Standard environmental specifications of the inverter *1 0 to +50°C for the FR-A800-GF. *2 0 to +40°C for the FR-A800-GF. *3 Temperature applicable for a short time, for example, in transit. *4 For the installation at an altitude above 1000 m, consider a 3% reduction in the rated current per 500 m increase in altitude. *5 2.9 m/s 2 or less for the FR-A840-04320(160K) or higher.

Temperature The permissible surrounding air temperature of the inverter is between -10°C and +50°C (-10°C and +40°C at the SLD rating). Always operate the inverter within this temperature range. Operation outside this range will considerably shorten the service (The permissible surrounding air temperature of the FR-A800-GF is between 0 and +50°C (0 and +40°C for the SLD rating).) lives of the semiconductors, parts, capacitors and others. Take the following measures to keep the surrounding air temperature of the inverter within the specified range. Measures against high temperature Use a forced ventilation system or similar cooling system.

(Refer to page 42 .) Install the enclosure in an air-conditioned electric chamber. Block direct sunlight. Provide a shield or similar plate to avoid direct exposure to the radiated heat and wind of a heat source. Ventilate the area around the enclosure well. Measures against low temperature Provide a space heater in the enclosure. Do not power OFF the inverter. (Keep the start signal of the inverter OFF.) Sudden temperature changes Select an installation place where temperature does not change suddenly. Avoid installing the inverter near the air outlet of an air conditioner. If temperature changes are caused by opening/closing of a door, install the inverter away from the door. 38 2.

INSTALLATION AND WIRING 2.3 Installation of the inverter and enclosure design Item Description Surrounding air temperature LD, ND (initial setting), HD -10 to +50°C*1 (non-freezing) Measurement position Inverter 5 cm 5 cm Measurement 5 cm position SLD -10 to +40°C*2 (non-freezing) Ambient humidity With circuit board coating (conforming to IEC 60721-3-3:1994 3C2/3S2): 95% RH or less (non-condensing) Without circuit board coating: 90% RH or less (non-condensing) Storage temperature -20 to +65°C*3 Atmosphere Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt) Altitude Maximum 2500 m*4 Vibration 5.9 m/s2 or less*5 at 10 to 55 Hz (in either X, Y, or Z direction)