Mitsubishi FR-A800 — 2.6.1 Details on the control circuit terminals

Output signal 1 2 3 4 5 6 7 8 9 10 *1 The terminal function can be selected by Pr.190 to Pr.196 (Output terminal function selection) . (Refer to page 490 .) *2 Terminal FM is provided in the FM-type inverter. *3 Terminal CA is provided in the CA-type inverter. 71 2. INSTALLATION AND WIRING 2.6 Control circuit Type Terminal symbol Common Terminal name Terminal function description Rated specification Refer to page Relay A1, B1, C1*1 — Relay output 1 (fault output) 1 changeover contact output that indicates that an inverter's protective function has been activated and the outputs are stopped. Fault: discontinuity across B and C (continuity across A and C), Normal:

continuity across B and C (discontinuity across A and C) Contact capacity: 230 VAC 0.3 A (power factor = 0.4), 30 VDC 0.3 A 490 A2, B2, C2*1 — Relay output 2 1 changeover contact output 490 Open collector RUN*1 SE Inverter running The output is in LOW state when the inverter output frequency is equal to or higher than the starting frequency (initial value: 0.5 Hz). The output is in HIGH state during stop or DC injection brake operation. Permissible load: 24 VDC (27 VDC at maximum) 0.1 A (The voltage drop is 2.8 V at maximum while the signal is ON.) The open collector transistor is ON (conductive) in LOW state. The transistor is OFF (not conductive) in HIGH state.

490 SU*1 SE Up to frequency The output is in LOW state when the output frequency is within the set frequency range ±10% (initial value). The output is in HIGH state during acceleration/deceleration and at a stop. Fault code (4 bits) output. (Refer to page 510.) 501 OL*1 SE Overload warning The output is in LOW state when stall prevention is activated by the stall prevention function. The output is in HIGH state when stall prevention is canceled. 448 IPF*1 SE Instantaneous power failure The output is in LOW state when an instantaneous power failure occurs or when the undervoltage protection is activated.

647, 654 FU*1 SE Frequency detection The output is in LOW state when the inverter output frequency is equal to or higher than the preset detection frequency, and is in HIGH state when it is less than the preset detection frequency. 501 Pulse FM*2 SD For meter Among several monitor items such as output frequency, select one to output it via these terminals. The signal is not output during an inverter reset. The size of output signal is proportional to the magnitude of the corresponding monitor item. Use Pr.55, Pr.56, and Pr.866 to set full scales for the monitoring output frequency, output current, and torque. (Refer to page 474.) Output item:

Output frequency (initial setting) Permissible load current: 2 mA, pulse for full scale: 1440 pulses/ s 474 NPN open collector output This terminal can be used for open collector outputs depending on the Pr.291 setting. Maximum output pulse: 50k pulses/s, permissible load current: 80 mA 413 Analog AM 5 Analog voltage output Output item: Output frequency (initial setting) Output signal: 0 to ±10 VDC, permissible load current: 1 mA (load impedance 10 kΩ or more), resolution: 13 bits 474 CA*3 5 Analog current output Load impedance: 200 to 450 Ω, output signal: 0 to 20 mADC 474