Mitsubishi FR-A800 — 2.6.3 Wiring of control circuit

2. Crimp the terminals on the wire. Check the condition of the crimp terminals after crimping. Do not use the crimp terminals of which the crimping is Insert the wire into a crimp terminal, making sure that 0 to 0.5 mm of the wire protrudes from the end of the sleeve. inappropriate, or the face is damaged. Unstranded wires Wire Wire Sleeve Sleeve 0 to 0.5mm 0 to 0.5mm Crumpled tip Wires are not inserted into the sleeve Damaged Crimp terminals commercially available (as of October 2020) Phoenix Contact Co., Ltd. *1 A ferrule terminal with an insulation sleeve compatible with the MTW wire which has a thick wire insulation. *2 Applicable for terminals A1, B1, C1, A2, B2, C2. NICHIFU Co., Ltd.

No. 3. Insert the wire into the terminal block. When using single wire or stranded wire without crimp terminal, push an open/close button all the way down with a flathead screwdriver, and insert the wire. Open/close button Flathead screwdriver When using stranded wires without a blade terminal, twist enough to avoid short circuit with a nearby terminals or wires. Place the flathead screwdriver vertical to the open/close button. In case the blade tip slips, it may cause an inverter damage or injury. 76 2. INSTALLATION AND WIRING 2.6 Control circuit Wire gauge (mm2) Ferrule part No. With insulation sleeve Without insulation sleeve For UL wire*1 Crimping tool model No.

Without insulation sleeve For UL wire*1 0.3 AI 0,34-10TQ — — CRIMPFOX 6 0.5 AI 0,5-10WH — AI 0,5-10WH-GB 0.75 AI 0,75-10GY A 0,75-10 AI 0,75-10GY-GB 1 AI 1-10RD A 1-10 AI 1-10RD/1000GB 1.25, 1.5 AI 1,5-10BK A 1,5-10 AI 1,5-10BK/1000GB*2 0.75 (two-wire produc t) AI-TWIN 2×0,75-10GY — — Wire gauge (mm2) Blade terminal part No. Insu Crimpin lation cap part No. 0.3 to 0.75 BT 0.75-11 VC 0.75 NH 69 NOTE