Victron Energy · MultiPlus-II 4k5 & 6k5 GX · 2 pp.

Victron MultiPlus-II 4k5 & 6k5 GX Inverter/Charger Manual PDF

Read online

Related manuals

Document text

New models: more power per kg and per dmі, and better high temperature performance A MultiPlus-II with LCD and GX functionality The MultiPlus-II GX integrates a MultiPlus-II inverter/charger and a GX device with a 2 x 16 character display. Display and WiFi The display reads battery, inverter and solar charge controller parameters. The same parameters can be accessed with a smartphone or other WiFi enabled device. GX device The integrated GX device includes: A BMS-Can interface. This can be used to connect to a compatible CAN-bus managed battery. Note that this not a VE.Can compatible port. A USB port. An Ethernet port. A VE.Direct port.

Applications The MultiPlus-II GX is intended for applications where additional interfacing with other products and/or remote monitoring is required, such as on-grid or off-grid energy storage systems and certain mobile applications. Parallel and three phase operation Only one GX unit is needed in case of Parallel and three phase operation. MultiPlus-II 6k5 GX Standard marine, mobile or off-grid application Loads that should shut down when AC input power is not available can be connected to a second output (not shown). These loads will be taken into account by the PowerControl and PowerAssist function in order to limit AC input current to a safe value when AC power is available.

Standard mobile or off-grid application with external current sensor Maximum current sensing range: 100 A. Grid parallel topology with MPPT solar charge controller The MultiPlus-II will use data from the external AC current sensor (must be ordered separately) or power meter to optimise self-consumption and, if required, to prevent grid feed. In case of a power outage, the MultiPlus-II will continue to supply the critical loads. Grid in-line topology with PV inverter PV power is directly converted to AC.

The MultiPlus-II will use excess PV power to charge the batteries or to feed power back into the grid, and will discharge the battery or use power from the grid to supplement a shortage of PV power. In case of a power outage, the MultiPlus-II will disconnect the grid and continue to supply the loads. MultiPlus-II Inverter/Charger 4k5 & 6k5 GX 230V \

Page 1

VRM Portal Our free remote monitoring website (VRM) will display all system data in a comprehensive graphical format. System settings can be changed remotely via the portal. Alarms can be received by e-mail or push notification. VRM app Monitor and manage your Victron Energy system from your smart phone and tablet. Available for both iOS and Android. GX GSM A cellular modem; providing a mobile internet for the system and connection to Victron Remote Management (VRM). Optional: outdoor GSM antenna and GPS antenna.

For more detail please enter GX GSM in the search box on our website Current sensor 100 A:50 mA To implement PowerControl and PowerAssist and to optimize self-consumption with external current sensing. Maximum current: 100 A. Length of connection cable: 1 m. Digital Multi Control Panel A convenient and low-cost solution for remote monitoring, with a rotary knob to set PowerControl and PowerAssist levels. Connection Area Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands E-mail:

sales@victronenergy.com | www.victronenergy.com MultiPlus-II GX 230V 48/ 4k5/55-32 48/6k5/100-50 PowerControl & PowerAssist Yes Transfer switch 32 A 50 A Maximum AC input current 32 A 50 A INVERTER DC Input voltage range 38 – 60 V Output 230 V ±2 % 50 Hz ± 0.1% (1) Cont. output power at 25 °C 4 kW 6 kW Cont. output power at 40 °C 3,7 kW 5,7 kW Cont.

output power at 65 °C 3 kW 4,6 kW Time-limited power 1 (cold start) 4,5 kW/2h 6,5 kW/4h Time-limited power 2 (cold start) 6 kW/25min 8 kW/1h Max apparent feed-in power 4 kW 6 kW Peak power 7 kW/1min 11 kW/1min Maximum efficiency 95 % 96 % Zero load power 20 W 28 W Zero load power in AES mode 13 W 18 W Zero load power in Search mode 8 W 8 W CHARGER AC Input voltage range 187-265 V AC Input frequency range 45 – 65 Hz Charge voltage 'absorption' 57,6 V Charge voltage 'float' 55,2 V Storage mode 52,8 V Max. battery charge current at 25 °C 55 A 100 A Max. battery charge current at 40 °C 50 A 95 A Battery temperature sensor Optional. Order number:

ASS000001000 Compatible battery chemistries Lithium, Lead-acid, Zinc-Bromine and more(3) GENERAL Auxiliary output Yes (32 A) Interfaces BMS-Can, USB, Ethernet, VE.Direct, Wi-Fi External AC current sensor (optional) 100 A Programmable relay (4) Yes Protection (2) a–g VE.Bus communication port For parallel and three-phase operation, remote monitoring and system integration VE.Bus communication port General-purpose communication port Yes, 2x Remote on-off Yes Operating temperature range -40 to +65 °C (fan-assisted cooling) Maximum humidity (non-condensing) 95 % Maximum altitude 2000 m ENCLOSURE Material & Colour Steel, blue RAL 5012 Protection category IP21 Battery-connection M8 bolts 230 V AC connection Screw terminals 13 mm² (6 AWG) Weight 21,4 kg 29 kg Dimensions (hxwxd) 590 x 275 x 149 mm 644 x 320 x 150 mm STANDARDS Safety EN-IEC 60335-1, EN-IEC 60335-2-29, EN-IEC 62109-1, EN-IEC 62109-2 Emission, Immunity EN 55014-1, EN 55014-2 EN-IEC 61000-3-2, EN-IEC 61000-3-3 IEC 61000-6-1, IEC 61000-6-2, IEC 61000-6-3 Uninterruptible power supply Certification pending Anti-islanding Certification pending 3) Other chemistries are possible as well, providing the charger is configured according to the battery manufacturer’s specification.

4) Programmable relay which can be set for general alarm, DC under voltage or genset start/stop function. AC rating: 230 V / 4 A, DC rating: 4 A up to 35 VDC and 1 A up to 60 VDC. 1) Can be adjusted to 60 Hz 2) Protection key: a) output short circuit b) overload c) battery voltage too high d) battery voltage too low e) temperature too high f) 230 VAC on inverter output g) input voltage ripple too high

Page 2