omron — Standard Specification List

■ Terminal Block Specifications ● Terminal Block Position Control circuit terminal block A Control circuit terminal block B Relay output terminals Input logic selector RS-485 communication/ Operator selector Main circuit terminal block Frequency reference/ Run command selector Note.

This illustration shows the terminal block with the front cover removed ● Specifications of Main Circuit Terminals Terminal Arrangement 3G3MX-A2002 to A2007 3G3MX-AE002 to AE004 Terminal Arrangement 3G3MX-A2015 to A2037 3G3MX-A4004 to A4037 3G3MX-AE007 to AE022 Terminal Arrangement 3G3MX-A2055 to A2075 3G3MX-A4055 to A4075 Short-circuit bar Upper RB +1 P/+2 N/- Upper S/L2 T/L3 U/T1 V/T2 W/T3 R/L1 Upper R/L1 S/L2 T/L3 U/T1 V/T2 W/T3 Lower +1 Lower Lower Short-circuit bar 30 Multi-functional Compact Inverters SYSDRIVE MX Series RB +1 P/+2 N/- R/L1 S/L2 T/ L3 U/ T1 V/ T2 W/T3 2 N/- RB Terminal symbol Terminal name Function Connection example R/L1, S/L2, T/L3 Main power supply input terminal Connect the input power supply.

Motor ELB Power supply Do not remove the short-circuit bar between +1 and P/+2 when a DC reactor is not connected. U/T1, V/T2, W/T3 Inverter output terminal Connect to the motor. +1, P/+2 External DC reactor terminal Normally connected by the short-circuit bar. Remove the short- circuit bar between +1 and P/+2 when a DC reactor is connected. P/+2 RB External braking resistor connection terminal Connect the optional braking resistor. (If a braking torque is required) P/+2, N/- Regenerative braking unit connection terminal Connect optional regenerative braking units.

(If a braking torque is required) (if insufficient with only the built-in braking circuit) Ground terminal Ground (Connect to ground to prevent electric shock and reduce noise.)