Technical Note OMRON 2POTS OMRON 2POTS PLC CP2 Option Card This document explains how to: - Manually Adjust the Card - Change the Auxiliary Memory Values June 17, 2024

Page 1

Technical Note: OMRON 2POTS Table of Contents : 1. OMRON 2POTS Notes ......................................................................... Error! Bookmark not defined. Table of Figures Figure 1. PLC Settings Screen ..................................................................... Error! Bookmark not defined. Figure 2. 2POTS PLC Option Card ...............................................................................................................

3 Limitation on Liability Omron companies shall not be liable for special, indirect, incidental, or consequential damages, loss of profits or production or commercial loss in any way connected to the technical note, whether such claim is based in contract, warranty, negligence or strict liability. 2

Page 2

1. OMRON 2POTS

Technical Note: OMRON 2POTS 1. OMRON 2POTS OMRON 2POTS is a CP2 option card with two rotary POTs that can be manually adjusted (ie with a small screw driver). The POTs will be used to manually set two values stored in PLC auxiliary memory. The 2POTS module communicates with the CP2 PLC using the Host Link protocol with default serial communication settings as shown below. One 2POTS hardware module can be installed in either Slot #1 or Slot #2, but not both. Figure 1: PLC Settings Screen Figure 2: 2POTS PLC Option Card POT1 will change the value into auxiliary memory area A642. POT2 will change the value into auxiliary memory area A643.

The POT turned CW to full stop will output 255 and the POT turned CCW to full stop will output 0 to auxiliary memory. All other output will be a linear representation of the POTs position between 0-255. 3