EVADA — 9.6.2 Cable connection

2.When installing the inverter, do not connect the zero wire, live wire and ground wire of the inverter reversely or wrongly, so as to avoid electrical short circuit 3.The inverter shall not be connected with unbalanced load and half wave rectifier load.

9.6.2 Cable connection 1 2 3 4 5 6 7 8 9 NL FA COM 4 8 5 - Parallel interface 4 8 5 + 10 11 12 13 14 15 16 17 18 Schematic diagram of panel and wiring terminal(6Kva) AC-INPUT AC-OUTPUT L N L - N DC-INPUT + 1 2 3 4 5 6 7 8 9 4 8 5 + NL FA COM 4 8 5 - AC-OUTPUT L N AC-INPUT L N DC-INPUT - DC-INPUT + 17 16 15 14 Schematic diagram of panel and wiring terminal(9~15Kva) Definition of each serial number : 12 13 10 11 9.6.2.1 Wiring instructions 1) Connect the ground wire (PE) of the machine to the ground wire of the rack.

2) Connect the positive and negative poles of the DC bus (48VDC) with the positive and negative board terminals in the machine wiring block respectively, and pay attention to the correct polarity. 3) After the wiring is completed, connect the DC bus lead with the DC 48VDC power supply system. In the wiring back road between the DC bus and the machine, it is necessary to install a suitable air switch to prevent fire accidents caused by short circuit. 4) Each inverter module needs to have its own DC input shunt.

18 1 Handle 7 Ope ration indicator 13 Grounding nut 2 Snap switch 8 Fau lt indicator 14 AC input zero line (n) 3 Air inlet 9 Mo dule fixing hole 15 AC input live wire (L) 4 LCD display panel 10 DC Input -48V 16 AC output zero line (n) 5 On/off button 11 DC Input 0V 17 AC output live wire (L) 6 Page turning key 12 Co mmunication interface 18 Parallel interface