Ethernet Communication Module IFD9506 7.2 Exception Codes Supported 7.3 Device Type & Device Address Discrete input Device type Modbus address (Hex) 5-digit Modbus address (Dec) 6-digit Modbus address (Dec) Number RX 0x0400 ~ 0x0402 11025 ~ 11027 101025 ~ 101027 3 Holding register Device type Modbus address (Hex) 5-digit Modbus address (Dec) 6-digit Modbus address (Dec) Number BR 0x0000 ~ 0x00FF 40001 ~ 40256 400001 ~ 400256 64 AL 0x0200 ~ 0x0202 40513 ~ 40515 400513 ~ 400515 3 MB 0x2000 ~ 0x20FF 48193 ~ 48448 408193 ~ 408448 256 MW 0x2200 ~ 0x23FF 48705 ~ 49216 408705 ~ 409216 512 MIP 0x2400 ~ 0x24FF 49217 ~ 49471 409217 ~ 409471 256 8 Setting up Software This section gives instructions on how to set up IFD9506 by DCISoft and explanations on each setup page.

IFD9506 is set up by UDP port 20006; therefore, you have to be aware of the relevant settings of the firewall. See the explanations below on the software. 8.1 Setting up Communication & Searching for Modules in DCISoft ѓ Broadcast search 1. Open DCISoft on the PC and click on the “IP Search” icon. DVP-PLC Application Manual 16 Function code Explanation Devices supported 0x10 Write multiple holding registers BR, AL, MB, MW, MIP 0x17 Read/write multiple holding registers BR, AL, MB, MW, MIP Exception code Explanation 0x01 Illegal function 0x02 Illegal data addresss 0x03 Illegal data value 0x04 Slave device failure 0x0A Gateway path unavailable 0x0B Gateway target device failed to respond