Data Map: Level Products Applicaton Layer Note: The data maps shown for the Write and Read Blocks apply if P762 is set to the default values (see page 15). If any of these values is changed, the data map will be shortened and the configuration will change. (See Appendix A – Reducing the amount of data being transferred over the Bus, on page 46.) This section describes the meaning of the data read from and written to the Siemens Milltronics SmartLinx instrument. Write Block Word 0: Point-on-Priority Bits 00-09 set the priority status of corresponding indexed points 1 to 10.

bit status 0 = normal 1 = priority For example, if bits 00 and 02 are set to 1, then points 3 and 1 are on priority scan. All other bits are reserved and contain 0.

Page 24 SmartLinx PROFIBUS DP – INSTRUCTION MANUAL 7ML19981AQ03 Word Description Access Data Type 0 measurement point-on-priority direct bitmapped 1 parameter number MPA integer 2 secondary index (mark) integer 3 decimal place integer 4 format 0/1 5 parameter number integer 6 primary index (point) integer 7 secondary index (mark) integer 8 new value SPA integer 9 decimal place integer 10 format 0/1 11 read/write flag 0/1 12 operating mode direct 0/1 bit 09 08 07 06 05 04 03 02 01 00 index 10 9 8 7 6 5 4 3 2 1 bit 09 08 07 06 05 04 03 02 01 00 index 0 0 0 0 0 0 0 1 0 1