Original Read Block Data map for Level Products Mass Dynamics Products The SmartLinx map 1 is controlled by the values of the indices of P762. By turning on an index (setting the value to one or more), you activate both the read and write blocks associated with that index. The table below shows which values in the read/write blocks are turned on by each P762 index. Appendix A 1.

For examples of the data maps before modification, see pages 54 and 55 7ML19981AQ03 SmartLinx PROFIBUS DP – INSTRUCTION MANUAL Page 51 Words Description Access Data Type 0 instrument status bitmapped 1-10 point reading direct integer 11-20 point alarm and status bitmapped 21-30 returned values MPA integer 31 decimal place integer 32 format 0/1 33 parameter number integer 34 parameter secondary index integer 35 parameter integer 36 parameter primary index integer 37 parameter secondary index integer 38 value SPA integer 39 decimal place integer 40 format 0/1 41 read/write flag 0/1 Name of area P762 Point Value Read area turned On Write area turned on BW500, SF500 BW500/L status 1 1 1 instrument status ------------------- rate 2 1 1 rate ------------------- load 3 1 1 load ------------------- speed 4 1 1 speed ------------------- total 5 1 1 total 1 ------------------- total 2 relay status 6 1 1 relay status ------------------- DI status 7 1 1 discrete input status -------------------