Communication Set-up The SmartLinx DeviceNet module is a slave device on the network. It is a DeviceNet Group 2 server only as determined in the predefined master/slave connection definitions. The data size of the input and output modules is dependent on P762, and on the type of unit the module is plugged into (see the three categories below). The following instructions assume that P762 is set to the default values shown in the chart on page 13. There are three categories of device: 1. AiRanger/ SITRANS LU Series, CraneRanger series, and InterRanger DPS 300 2. EnviroRanger ERS 500, MultiRanger 100/200, HydroRanger 200 3.

Milltronics BW500, Milltronics SF500 AiRanger / SITRANS LU Series, CraneRanger and InterRanger DPS 300 This card only supports polled I/O with the following setup: • I/O connection #1 input size of 64 bytes. • I/O connection #1 output size of 26 bytes. Some configurations may also require some of the following information: • Device Type is 12(0x0c) • Product code is 7 • Vendor ID is 90 (0x5a) EnviroRanger ERS 500, MultiRanger 100/200, HydroRanger 200 This card only supports polled I/O with the following setup: • I/O connection #1 input size of 84 bytes. • I/O connection #1 output size of 26 bytes. Some configurations may also require some of the following information:

• Device Type is 12(0x0c) • Product code is 12 • Vendor ID is 90 (0x5a) Milltronics BW500, Milltronics SF500 This card only supports polled I/O with the following setup: • I/O connection #1 input size of 68 1 bytes. • I/O connection #1 output size of 38 bytes. Some configurations may also require some of the following information: • Device Type is 12(0x0c) • Product code is 12 • Vendor ID is 90 (0x5a) Communicatons Set-up 1. 68 is the correct value for BW500/SF500 units that have firmware V 3.05 or greater and have all the values of P762 turned on. For older units, the input size is 62. 7ML19981BH02 SmartLinx DeviceNet – Instruction Manual Page 11