Siemens — Software Compatibility

Installation The SmartLinx module is either shipped installed in the Siemens Milltronics instrument or shipped separately for on-site installation. Refer to the manual of your Siemens Milltronics instrument for details on module location and installation. Compatibility For the SmartLinx Device Net card there are different hardware and software configurations available depending on the equipment used. Software Compatibility If a device is SmartLinx ready, it will work with the correct SmartLinx card for that device. However, if the firmware version is a lower number than the one listed below, the P762 Map Element Selection Parameter will not be available.

Also, for the BW500 and the SF500, the read block will be a smaller size. installation Retrofits If you are replacing an older SmartLinx device with a new SmartLinx device, and you are using any product other than the BW500 or SF500, then you can use the default values for P762. If you are replacing a BW500 or SF500 with a new device, then set P762 primary index 15 = 0, and P762 primary index 16 = 0. Page 4 SmartLinx DeviceNet – Instruction Manual 7ML19981BH02 Product Software Rev. Product Software Rev.

AiRanger XPL Plus / SITRANS LU 10 5.23 Milltronics SF500 3.05 AiRanger DPL Plus / SITRANS LU 02 Milltronics BW500 AiRanger SPL / SITRANS LU 01 MultiRanger 100 1.04 InterRanger DPS 300 MultiRanger 200 1.03 HydroRanger 200 EnviroRanger ERS 500 5.06