DeviceNet Slave Communication Module IFD9502 into H’0001 and re-power IFD9502. Please note that doing so can only recover the current I/O data mapping in PLC. „ Class 0x99 Data Config Instance0: Instance1 (DTA): Data_in refers to the data transmitted from DeviceNet master to DTA. Data_out refers to the data transmitted from DTA to DeviceNet master.

Common Services DVP-PLC Application Manual 15 Attribute ID Access rule Name Data type 1 Get Revision UINT Attribute ID Access rule Name Data type Default 1 Get/Set Reset parameter USINT H’0000 2 Get/Set Input data length USINT 2 words 3 Get/Set Output data length USINT 2 words 11 Get/Set Data in [0] _ UINT H’4701 12 Get/Set Data in [1] _ UINT H’4719 (for DTA) 13 Get/Set Data in [2] _ UINT H’FFFF 14 Get/Set Data in [3] _ UINT H’FFFF 15 Get/Set Data in [4] _ UINT H’FFFF 16 Get/Set Data in [5] _ UINT H’FFFF 17 Get/Set Data in [6] _ UINT H’FFFF 18 Get/Set Data in [7] _ UINT H’FFFF 25 Get/Set Data out [0] _ UINT H’4700 26 Get/Set Data out [1] _ UINT H’4719 (for DTA) 27 Get/Set Data out [2] _ UINT H’FFFF 28 Get/Set Data out [3] _ UINT H’FFFF 29 Get/Set Data out [4] _ UINT H’FFFF 30 Get/Set Data out [5] _ UINT H’FFFF 31 Get/Set Data out [6] _ UINT H’FFFF 32 Get/Set Data out [7] _ UINT H’FFFF Implemented for Class Instance Service Code Service name Instance 0x05 Yes Yes Reset 0x0E Yes Yes Get Attribute single _ _ 0x10 No Yes Set Attribute single _ _