Lenze — 4.6.5 Devices in the range 145 695 A ( 75 400 kW)

4 4.6 4.6.5 Single-axis controllers Wiring Devices in the range 145 ... 695 A (75 ... 400 kW) DC bus Mains Motor temperature monitoring  4.6-42 EDS94SPP101 EN 3.1-04/2007 Terminal X100 Labelling Description +Ug -Ug Terminal data Max. conductor cross-section Tightening torque Screw drive [mm2] [AWG] [Nm] [lb-in] 2 x 400 3 x 150 2 x 750 mcm 3 x 350 mcm 19 168 Terminal X100 Marking Description Connection with ring cable lug for M10 SSP94KL801 L1 L2 L3 Connection of the mains phases  Connection for the PE conductor on the supply side Terminal data Max. conductor cross-section Tightening torque Screw drive [mm2] [AWG] [Nm] [lb-in] Device size 10:

E94ASxE4604 E94ASxE5724 E94ASxE6354 E94ASxE6954 2 x 400 3 x 150 2 x 750 mcm 3 x 350 mcm 19 168 WAF 16 Terminal X106 Labelling Description SSP94X6106 T1 T2 Motor temperature monitoring with PTC element (type-A sensor, switching performance according to EN 60947-8 for type-A tripping units) or thermostat (NC contact). Terminal data Max. conductor cross-section Tightening torque Screw drive [mm2] [AWG] [Nm] [lb-in] Flexible 2.5 12 0.5 ... 0.6 4.5 ... 6.2 Slot 0.6 x 3.5 With wire end ferrule