Lenze — 5.3.3 Overcurrent operation

5 5.3 5.3.3 Multi-axis controllers Rated data Overcurrent operation 5.3.3 Overcurrent operation The controllers are designed for two overcurrent modes: ƒ 5-s-cycle c – 0.5 s load period with peak current  – 4.5 s recovery time with limited current  ƒ 3-min cycle d – 1 min load period with peak current  – 2 min recovery time with limited current  A load period must be followed by a recovery time. During the recovery time the current must not exceed the value given. The values given refer to the rated output current I aN8 . I [%] aN8   100   t 0 0.5 s 4.5 s 1 min 2 min 9400SSP008 Fig. 5.3-1 Overcurrent capacity at 45° C  Peak current for 0.5 s c 5-s cycle  Max.