6 6.6 6.6.2 DC power supply modules Wiring Safety notes for the installation according to U L or U R 6.6.2 Safety notes for the installation according to U L or U R E94APNE0104/E94APNE0364 Warnings! ƒ Maximum surrounding air temperature: 55 °C. ƒ Branch circuit protection: Suitable for use on a circuit capable of delivering not more than 5000 rms symetrical amperes, 500 V max., when protected by H, K5 or CC fuses. ƒ Voltage of the fuses must at least be suitable with the input voltage of the drive. ƒ Control card protection: External fuse for 24 Vdc supply voltage of control terminal X11. Rated 4 A DC fuse UL248-14. ƒ Use 60/75 °C copper wire only, except for control circuits.
E94APNE1004/E94APNE2454 Warnings! ƒ Maximum surrounding air temperature: 55 °C. ƒ Branch circuit protection: Suitable for use on a circuit capable of delivering not more than 18000 rms symetrical amperes, 500 V max., when protected by H or K5 fuses. ƒ Voltage of the fuses must at least be suitable with the input voltage of the drive. ƒ Use 60/75 °C copper wire only, except for control circuits. 6.6-2 EDS94SPP101 EN 3.1-04/2007 Branch circuit protection Type Fuse [A] E94APNE0104 15 E94APNE0364 40 Branch circuit protection Type Fuse [A] E94APNE1004 100 E94APNE2454 250