DC power supply modules Wiring Terminal assignment 6 6.6 6.6.9 Mains C ti f th l id PE d t Connection for the supply-side PE conductor C ti f th l id PE d t Connection for the supply-side PE conductor DC bus 6.6-11 EDS94SPP101 EN 3.1-04/2007 Terminal X111 Labelling Description L1 L2 L3 Terminal X112 Labelling Description L1 L2 L3 Terminal data Max. conductor cross-section Tightening torque Screw drive [mm2] [AWG] [Nm] [lb-in] Device size 4: Connection with ring cable lug M8 50 (2 x 25) 1/0 - 8 71 SW13 Device size 5: Connection with ring cable lug M10 120 (2 x 50) 4/0 (2 x 1/0) 15 133 SW15 Terminal X111 Labelling Description Fig.
6.6-5 +UG -UG Connection of DC-bus voltage Cables routed upwards Terminal X112 Labelling Description Fig. 6.6-5 +UG -UG Connection of DC-bus voltage Cables routed downwards Terminal data Max. conductor cross-section Tightening torque Screw drive [mm2] [AWG] [Nm] [lb-in] Device size 4: Connection with ring cable lug M8 70 (2 x 35) 2/0 - 8 71 SW13 Device size 5: Connection with ring cable lug M10 150 (2 x 70) 300 mcm (2 x 2/0) 15 133 SW15