Lenze — 4.3.4 Operation at rated mains voltage 500 V

4 4.3 4.3.4 Single-axis controllers Rated data (devices for 400/500V mains) Operation at rated mains voltage 500 V I aN2 Rated value of permanent output current at a frequency of ≥ 0 Hz I aM2 Maximum output current (overload current) z Periodic load change of 0.5 s with I aM2 and recovery time of 4.5 s with 75 % I aN2 I aN4 , I aN8, I aN16 Rated value of permanent output current at a frequency of ≥ 5 Hz (reduce to 0.66 * I aNx for 0 ...

5 Hz) I aM4 , I aM8 Maximum output current (overload current) z Periodic load change of 0.5 s with I aMx and recovery time of 4.5 s with 75 % I aNx z Can be achieved using the setting ”x kHz fixed” in C00018 bold Nominal value I aN 3) Operation with permanent currents > I aN8 requires an external mains choke.

 4.3-12 EDS94SPP101 EN 3.1-04/2007 Output currents [A] at switching frequency 2 kHz 4 kHz 8 kHz 16 kHz Type IaN2 IaM2 IaN4 IaM4 IaN8 IaM8 IaN16 E94ASxE0024 1.9 3) 6.0 1.9 3) 6.0 1.3 4.2 1.0 E94ASxE0034 3.1 3) 10.0 3.1 3) 10.0 2.2 7.0 1.6 E94ASxE0044 5.0 3) 16.0 5.0 3) 16.0 3.5 11.2 2.6 E94ASxE0074 8.8 3) 21.0 8.8 3) 21.0 6.1 14.7 4.6 E94ASxE0134 16.3 3) 39.0 16.3 3) 39.0 11.4 27.3 8.5 E94ASxE0174 20.6 3) 49.5 20.6 3) 49.5 14.4 34.7 10.8 E94ASxE0244 29.4 3) 58.8 29.4 3) 58.8 20.6 41.1 15.4 E94ASxE0324 38.4 76.8 33.6 67.2 28.0 61.6 16.8 E94ASxE0474 47.0 94.0 41.1 82.2 35.8 71.6 24.7 E94ASxE0594 59.0 118 51.6 103.2 35.9 71.8 31.0 E94ASxE0864 86.0 172 75.3 150.6 63.9 127.8 42.5 E94ASxE1044 104.0 208 91.0 182 68.3 136.6 54.6 E94ASxE1454 145 261 145 261 89 161 - E94ASxE1724 172 310 172 310 105 189 - E94ASxE2024 202 364 202 364 115 206 - E94ASxE2454 245 441 209 376 140 252 - E94ASxE2924 292 526 250 450 167 301 - E94ASxE3664 366 659 313 563 210 378 - E94ASxE4604 460 828 368 662 228 410 - E94ASxE5724 572 1030 458 824 250 450 - E94ASxE6354 635 1143 508 914 278 500 - E94ASxE6954 695 1251 556 1001 305 549 -