Lenze — 4.5.2 Devices in the range 2 24 A ( 0.37 11 kW)

4 4.5 4.5.2 Single-axis controllers Mechanical installation Devices in the range 2 ... 24 A (0.37 ... 11 kW) Mounting grid We recommend to provide the mounting plate with a grid pattern of M5 threaded holes for attaching the devices. This preparation enables easy attachment of the devices and the device sizes 1, 2, ... n can thus be mounted directly adjacent to each other.  Note! ƒ M5 screw and washer assemblies or hexagon socket screws with washers are permitted. ƒ Tightening torque: 3.4 Nm / 30 lb-in. ƒ In the installation backplane, the screwed connection may not jut out more than 7 mm. 9400SSP0010 Fig. 4.5-1 Mounting grid for installation backplane and filter of device sizes 1 ...

3  Installation backplane without footprint filter (mains or RFI filter)  Installation backplane with footprint filter  Grid hole pattern for installation backplane (M5 threaded holes)  Grid hole pattern for footprint filter (M5 threaded holes)  Cable duct 1 ... 3 Device size, mounting holes used  4.5-2 EDS94SPP101 EN 3.1-04/2007