Lenze — 4.6.1 Important notes

Single-axis controllers Wiring Important notes 4 4.6 4.6.1 4.6 Wiring 4.6.1 Important notes  Danger! Dangerous voltage All power terminals remain live for at least three minutes after mains disconnection. Possible consequences: ƒ Death or severe injuries when touching the power terminals. Protective measures: ƒ Wait for at least three minutes before working on the power terminals. ƒ Check that all power terminals are deenergised.  Danger! Dangerous voltage The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC. Possible consequences: ƒ Death or severe injuries when the device is touched in the event of a fault. Protective measures:

ƒ Implement the actions required in the EN 61800-5-1. Especially: – Fixed installation – PE connection must conform to standards (PE conductor diameter ≥ 10 mm 2 or PE conductor must be connected twice)  Stop! The device contains components that can be destroyed by electrostatic discharge! Before working on the device, personnel must ensure that they are free of electrostatic charge by using appropriate measures.  4.6-1 EDS94SPP101 EN 3.1-04/2007