4 4.6 4.6.4 Single-axis controllers Wiring Devices in the range 32 ... 104 A (15 ... 55 kW) Mains IT system Stop! Overvoltage on components: In case of an earth fault in IT systems, incompatible overvoltages may occur in the plant. Possible consequences: Destruction of the device. Protective measures: When using the devices in IT systems, separate the internal connection of filters to the protective earth. For this purpose carry out the device-specific measure as described. 4.6-18 EDS94SPP101 EN 3.1-04/2007 Terminal X100 (left part) Labelling Description L1 L2 L3 PE Terminal data Max.
conductor cross-section Tightening torque Screw drive [mm2] [AWG] [Nm] [lb-in] 50 0 10 88.5 95 000 14 124