A90 series Inverter User Guide 9 Parameter List 9.1 Introduction to parameter list A90 series inverter parameter have 20 groups of parameters . F18 group is the monitoring parameter group, used to view the inverter status; F19 group for the fault/trip record group, used to view the details of the recent 3 trips. ★ Part of the invisible parameters is reserved, changes may cause the inverter to run is not normal. Please avoid operating such parameters. ★ Parameter attributes:
● parameters can be changed in any state ;〇 The running status can not be changed ; Ч Read-only parameters ; 9.2 Function Parameter List 42 F00 Basic Function Parameter Group F01 Motor 1 Parameter F02 Input Terminal Function Group F03 Output Terminal Function Group F04 Start/Stop Control Parameter Group F05 V/F Control Parameter Group F06 Vector Control Parameter Group F07 Protection Function Setting Group F08 Preset Speed and Simple PLC F09 PID Function Group F10 Communication Function Group F11 User-Defined Parameter Group F12 Keypad and Display Function Group F13 Torque Control Parameter Group F14 Motor 2 Parameter Group F15 Auxiliary Function Group F16 Customized Function Group F17 Virtual I/O Function Group F18 Monitoring Parameter Group F19 Fault Record Group No.
Function Range Unit Default Type F00 Basic Function Parameter Group F00.01 Drive Control Mode of Motor 1 0: V/F control (VVF) 1: Sensorless Vector Control (SVC) 0 〇 F00.02 Command Source Options 0: Keypad Control 1: Terminal Control 2: Communication Control 0 〇 F00.03 Terminal Control Mode Options 0: Terminal RUN for running, Terminal F/R for Forward/Reverse 1: Terminal RUN for forward, F/R reverse 2: Terminal RUN for forward, Xi stop, F/R reverse 3: Terminal RUN for running, Xi stop, F/R for Forward/Reverse 0 〇