sinee — 9.2 Function Parameter List

A90 series Inverter User Guide 46 F02.15 Positive/Negative Logic 1 of Digital Input Terminal D7 D6 D5 D4 D3 D2 D1 D0 **0 00000 〇 * * X6 X5 X4 X3 X2 X1 0: Positive Logic, Enabled at On/Disabled at Off 1: Negative Logic, Disabled at On/Enabled at Off F02.16 Positive/Negative Logic 2 of Digital Input Terminal D7 D6 D5 D4 D3 D2 D1 D0 *** ***00 〇 * * * * * * AI2 AI1 0: Positive Logic, Enabled at On/Disabled at Off 1:

Negative Logic, Disabled at On/Enabled at Off F02.17 Filter Times of Digital Input Terminal 0-100, 0 for No Filter, n for sampling once every n ms 2 〇 F02.18 X1 ON Delay Time 0.000~30.000 s 0.000 ● F02.19 X1 OFF Delay Time 0.000~30.000 s 0.000 ● F02.20 X2 ON Delay Time 0.000~30.000 s 0.000 ● F02.21 X2 OFF Delay Time 0.000~30.000 s 0.000 ● F02.22 X3 ON Delay Time 0.000~30.000 s 0.000 ● F02.23 X3 OFF Delay Time 0.000~30.000 s 0.000 ● F02.24 X4 ON Delay Time 0.000~30.000 s 0.000 ● F02.25 X4 OFF Delay Time 0.000~30.000 s 0.000 ● F02.31 Analog Input Function Ones Place: AI1 0: Analog Input 1: Digital Input (0 for less than 1V, 1 for over 3V, same to the last time for 1V-3V) Tens Place: AI2 0:

Analog Input 1: Digital input (the same as above) 00D 〇 F02.32 Analog Input Curve Options Ones Place: AI1 Curve 0: Curve 1 1: Curve 2 2: Curve 3 3: Curve 4 Tens Place: AI2 Curve 0: Curve 1 1: Curve 2 2: Curve 3 3: Curve 4 10D 〇 F02.33 Minimum Input of Curve 1 0.00~F02.35 V 0.10 ● F02.34 Setting Corresponding to Minimum Input of Curve 1 –100.0~+100.0 % 0.0 ●