sinee — 9.2 Function Parameter List

A90 series Inverter User Guide 63 F15.32 Brake Duty Ratio 20 - 100 (100 means that duty ratio is 1) % 100 ● F15.33 Running Mode of Set Frequency Lower Than Lower Limit Frequency 0: Run at Lower Limit Frequency 1: Stop 2: Run at Zero Speed 0 〇 F15.34 Fan Control 0: Run at Energization 1: Run at Start 2: Run at Intelligent Temperature Control 2 〇 F15.35 Over modulation Intensity 1.00 - 1.10 1.05 ● F15.39 Terminal Jog Priority 0: Disabled 1:

Enabled 0 〇 F15.40 Deceleration Time at Rapid Stop 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 1.00 ● F15.68 Power Price 0.00~100.00 1.00 〇 F15.69 Load Factor at Power Frequency 30.0~200.0 % 90.0 〇 F16 Customized Function Group F16.00 Industry Application 0:General purpose 1:Application of Air compressor 2:Applications of extruder 3:Application of pump 4:Application of fan 0 〇 F16.01 Set Length 1~65535(F16.13=0) 0.1~6553.5(F16.13=1) 0.01~655.35(F16.13=2) 0.001~65.535(F16.13=3) m 1000 ● F16.02 Pulse Count Per Meter 0.1 - 6553.5 100.0 ● F16.03 Set Count Value F16.04 - 65535 1000 ● F16.04 Designated Count Value 1 - F16.03 1000 ● F16.05 Set Timed Running time 0.0 - 6500.0, 0.0:

Disabled min 0.0 ● F16.06 Agent Password 0 - 65535 0 〇 F16.07 Set Accumulated Power-On Time Reach 0 - 65535, 0: Power-on Reach Time Protection Disabled h 0 〇 F16.08 Set Accumulated Running time Reach 0 - 65535, 0: Running time Reach Protection Disabled h 0 〇 F16.10 The percentage of analog output when the count value is zero 0.00~100.00 % 0.00 〇 F16.11 The percentage of analog output when the count value is the setting count value 0.00~100.00 % 100.00 〇