sinee — The prarmeter list of Extruder application macro

A90 series Inverter User Guide 10.3.2 Extruder application macro wiring diagram and parameter list 10V power supply,≤10mA frequency reference Analog input:0-10V Running speed ,output Analog output:0-10V ≤2mA Analog common Auxiliary power:24VDC,≤100mA Forward Reverse Digital input terminal Digital input terminal Digital input terminal External fault Fault reset Digital input terminal Digital output terminal Digital common terminal Relay output RS485 Communication port The prarmeter list of Extruder application macro F16.00=2:Extruder application, restore the factory value, the parameters shown in the following table: 69 10V AI1 GND M1 24V X1 X2 X3 X6 COM Y1 EC EB EA A+ A- No.

Function range Unit Default 0: Keypad Control F00.02 Command Source Options 1: Terminal Control 0 2: Communication Control Terminal Control Mode 1: Terminal RUN for forward, F/R for F00.03 1 Options reverse Main Frequency Source A F00.04 1: AI1 1 Options F00.14 Acceleration Time 1 s 25.00 F00.15 Deceleration Time 1 s 30.00 F00.16 Maximum Frequency Hz 50.00 F00.18 Upper Limit Frequency Hz 50.00 F00.19 Lower Limit Frequency Hz 0.00 F02.00 X1 Digital Input Function 1: Run Terminal “RUN” 1 F02.01 X2 Digital Input Function 2: Terminal R/F 2 F02.02 X3 Digital Input Function 23: External Fault Input 23 F05.00 V/F Curve Setting 1:

Multi-Dot Polyline V/F 1 Multipoint VF Voltage 0.0 - 100.0 (100.0= Motor Rated F05.02 % 2.0 Point V1 Voltage) Multipoint VF Voltage 0.0 - 100.0 (100.0= Motor Rated F05.04 % 5.5 Point V2 Voltage) V/F Stator Voltage F05.10 0.00-200.00(0.00 invalid) % 0.00 Compensation Gain V/F Slip Compensation F05.11 0.00-200.00(0.00 invalid) % 0.00 Gain