A90 series Inverter User Guide 71 Minimum Input of Curve F02.37 Analog input AI2 minimum V 2.10 2 Setting Corresponding to Minimum corresponds to the F02.38 Minimum Input of Curve % 0.0 frequency ratio 2 Maximum Input of Curve F02.39 Analog input AI2 maximum V 9.90 2 Setting Corresponding to The maximum input corresponds to F02.40 Maximum Input of Curve % 100.0 the frequency ratio 2 59: Dormancy Instructions F03.00 Y1 Output Function A relay that controls the dormant 59 pump F03.02 R1 Output Function 7: Inverter Fault 7 F05.00 V/F Curve Setting 4: Square V/F 4 Ones Place: continuious woking under instantaneous power failure Bus Voltage Control 0: Invalid 1:
valid F07.06 11 Options Tens Place:Overvoltage stall function selection 1: valid 0 – 20, 0: Fault Retry Disabled F07.14 Fault Retry Times Some faults allow retry to start 5 5 times F07.16 Failure retry interval 30s s 30.00 F09.00 PID Setting Source 0: Digital PID Setting F09.01 0 F09.01 Target pressure setting 0.0 ~ pressure sensor range F09.03 bar 1.0 F09.02 PID Feedback Source 2:AI2 2 F09.03 Pressure sensor range 0.1~6000.0 bar 10.0 F09.27 Sleep Option 0: Disabled 3 3:
Shutdown Output F09.29 Sleep Delay Time 0.0~6500.0 s 5.0 F09.30 0.00 - 100.00 (100.00 corresponds to Wake up Point % 9.00 F09.03) F09.31 Wake up Delay Time 0.0~6500.0 s 5.0 0:Target pressure F09.01 * wake up F09.39 Wake up mode selection coefficient 0 1:Wake up point (F09.30) 0.0 -100.0 (100.0 corresponds to F09.40 Wake up coefficient % 90.0 F09.01) F09.41 Pipeline overpressure 0.0 ~ pressure sensor range F09.03 bar 6.0 alarm pressure F09.42 Overpressure protection 0~3600(0 disabled) s 3 action time F18.17 PID Feedback display Display the current actual pressure bar XXX