A90 series Inverter User Guide Note 2: When the AI2 works as current signal, the S2 switch on control board should be selected ‘I’ mode. Note 3: To facilitate commissioning, default command source is keypad control, After debugging,Please change to the required command source. Note 4: Industry application macros can not be guaranteed to meet the needs of all users of the application,therefore,After selecting the application macro,It is also possible to set other parameters. 73 F00.21 Reverse Control 1: Prohibit Reverse 1 F00.30 Load Type 1: Normal Duty 1 F02.00 X1 Digital Input Function 1:
Run Terminal “RUN” 1 24:Switch Run Command to Keypad F02.01 X2 Digital Input Function When the terminal is enabled, switch 24 to manual mode F02.02 X3 Digital Input Function 9: Coast to Stop 9 F03.00 Y1 Output Function 1: Inverter Running 1 F04.00 Start Mode 1:Speed Tracking Start 1 Ones Place: the starting frequency 1: stop frequency Tens Place: search direction F04.08 Speed Tracking Method 11 1: current direction can not find the speed then search the reverse direction 0: Ramp-To-Stop F04.19 Stop Mode 1 1: Coast-to-Stop F05.00 V/F Curve Setting 4: Square V/F 4 Ones Place: continuious woking under instantaneous power failure Bus Voltage Control 0: Invalid 1:
valid F07.06 11 Options Tens Place:Overvoltage stall function selection 1: valid 0 – 20, 0: Fault Retry Disabled F07.14 Fault Retry Times Some failure allows retry to start 5 5 times F07.16 Fault retry interval 30s s 30.00 VX2 virtual terminal input 51: The main frequency source switch F17.01 51 function selection to F00.07 F17.09 VX1-VX8 status setting VX2 status with VY2 output status 00000 Virtual output terminal The VY2 state is determined by the F17.28 00000 control selection X2 terminal status