sinee — Руководство по эксплуатации Inverter A90 от SINEE (EN)

User Manual of A90 Series Inverter 104 proportional gain ACR-P2 F14.51 Torque current integral time constant ACR-T2 0.00-600.00 0.00: no integral ms 10.00 ● F14.52 Position loop gain 0.000 - 40.000 1.000 ● F14.53 SVC zero-frequency processing 0: braking 1: not processed 2: seal the tube 2 ○ F14.54 SVC zero-frequency braking current 50.0-400.0 (100.0 is the no-load current of the motor) % 100.0 ○ F14.55 SVC low-frequency excitation current 50.0-150.0 (100.0 is the no-load current of the motor) % 100.0 ○ F14.56 Voltage feedforward gain 0 - 100 % 0 ● F14.77 Acceleration/decelera tion time options of motor 2 0: the same as motor 1 1: acceleration and deceleration time 1 2:

acceleration and deceleration time 2 3: acceleration and deceleration time 3 4: acceleration and deceleration time 4 0 ○ F14.78 Maximum frequency of motor 2 1.00~600.00 Hz 50.00 ○ F14.79 Upper frequency limit of motor 2 Lower limit frequency F00.19 to maximum frequency F14.78 Hz 50.00 ● F14.80 V/F curve setting of motor 2 0: straight line V/F 1:

multi-point broken line V/F 0 ○ F14.81 Multi-point VF frequency F1 of motor 2 0.00 - F14.83 Hz 0.50 ● F14.82 Multi-point VF voltage V1 of motor 2 0.0~100.0 (100.0 = Rated voltage) % 1.0 ● F14.83 Multi-point VF frequency F2 of motor 2 F14.81 - F14.85 Hz 2.00 ● F14.84 Multi-point VF voltage V2 of motor 2 0.0-100.0 % 4.0 ● F14.85 Multi-point VF frequency F3 of motor 2 F14.83 to rated frequency of motor (reference frequency) Hz 5.00 ●