sinee — Руководство по эксплуатации Inverter A90 от SINEE (EN)

User Manual of A90 Series Inverter to F14.34 correspond to F01.00 to F01.34, which are motor nameplate parameters, motor parameters and encoder parameters; the function code F14.35 corresponds to F00.01, which is used to select the motor drive mode; the function codes F14.36 to F14.76 correspond to F06.00 to F06.40, which are vector control parameters; and the function code F14.77 is used to select the acceleration/deceleration time of the motor 2. Only the parameters of F14.72 are described below. For the rest of the parameters, refer to the relevant parameters of the motor 1. F14.77=0 : the acceleration/deceleration time of the motor 2 is the same as that of the motor 1.

For details, see the description of the function codes F15.03 to F15.09; acceleration/deceleration time 1/2/3/4, corresponding to the function codes F00.14, F14.77=1/2/3/4 : the acceleration/deceleration time of the motor 2 is fixed as the F00.15/F15.03, F15.04/F15.05, F15.06/F15.07 and F15.08, respectively. 7.16 Auxiliary Function Parameter Group of F15 Group 229 Function Default Function code name Parameter description Unit Attribute code setting F14.77 Acceleration/decelerati on time options of motor 2 0: the same as motor 1 1: acceleration and deceleration time 1 2: acceleration and deceleration time 2 3: acceleration and deceleration time 3 4:

acceleration and deceleration time 4 0 ○ Function Function code Default Parameter description Unit Attribute code name setting F15.00 Jog frequency 0.00 to maximum frequency F00.16 Hz 5.00 ● F15.01 Jog acceleration time 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 5.00 ● F15.02 Jog deceleration time 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) s 5.00 ●