User Manual of A90 Series Inverter The system has four groups (F00.14 and F00.15 in the first group) of acceleration and deceleration time options to meet different needs for normal operation. After completing the setting, the user can switch them via the combination of digital input functions “19: acceleration and deceleration time terminal 1” and “20: acceleration and deceleration time terminal 2”. For details, please see “Table 7-4 Function List of Multi-function Digital Input 231 ★: Unplug the keyboard during JOG running to stop the inverter. 1: Terminal control Select the digital input terminal function “4: forward jog (FJOG)” or “5: reverse jog (RJOG)”.
By default, if the function terminal is valid, the jog running command will be valid; and if the function terminal is invalid, the jog running command will be invalid. 2: Communication control If the host writes “0003H: JOG forward” or “0004: JOG reverse” to the register 7000H through the MODBUS protocol, the jog running command will be valid; if it writes “0007H: free stop”, the jog running command will be invalid.
Function Default Function code name Parameter description Unit Attribute code setting F15.03 Acceleration time 2 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.04 Deceleration time 2 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.05 Acceleration time 3 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.06 Deceleration time 3 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.07 Acceleration time 4 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.08 Deceleration time 4 0.00 - 650.00 (F15.13=0) 0.0 - 6500.0 (F15.13=1) 0 - 65000 (F15.13=2) s 15.00 ● F15.09 Fundamental frequency of acceleration and deceleration time 0:
maximum frequency F00.16 1: 50.00Hz 0 ○