User Manual of A90 Series Inverter Note: 1: The specifications of the wire are dependent on its voltage drop. Under normal circumstances, the voltage drop calculated by the following formula should be less than 5V. Voltage drop = 3 * wire resistivity (Ω/KM) * wire length (m) * rated current (A) * 10 -3 2: If the wire is in a plastic slot, it should be enlarged by one level. 3: The wire should be crimped to the round terminal suitable for the wire and terminal screw. 4: The specification of the ground wire should be the same as that of the power cable smaller than 16mm 2 . When the power cable is 16mm 2 or larger, the ground wire should not be smaller than 1/2 of the power cable.
36 A90-4T013B 6 750V wire A90-4T017B A90-4T025B M5 3.0~4.0 10 A90-4T032B A90-4T038B PB, +, -, R, S, T, U, V, W, A90-4T045B 16 A90-4T060 R, S, T, +, -, U, V, W M6 4.0~5.0 25 A90-4T075 25 A90-4T090 M8 9.0~10.0 35 A90-4T110 35 A90-4T150 M6 M10 4.0~5.0 17.0~22.0 60 A90-4T176 R, S, T, P, +, -, U, V, W 60 A90-4T210 90 A90-4T253 R, S, T, P, +, -, , U, V, W 90 A90-4T304 120