ABB ACS300 — ABB ACS300 AC Drives User Manual (EN)

Chapter 1 - Overview of This Manual Type Series Table 1-1 and Table 1-2 list the principal input and output rat- ings for each of the various ACS 300 type designations. The frame size assignments R0, R1 and R2 are used to identify the enclosure sizes and other characteristics of the various models. Table 1-1 ACS 300 AC drive types for 50 Hz and 60 Hz supplies. Input power supply 200 to 240 V. 1) Allowed for one minute every ten minutes at 50 ° C ambient. 2) The impedance of input power supply affects the input current. 3) The single underline (_) in the type designation stands for “0” or “1”.

ACS 300 User’s Manual 7 Type designation3) Frame Rated input current2) Output current Maximum permissible rated motor power Weight 1-phase I [A] 1 3-phase I [A] 1 Rated current I [A] N Short-term overload current I [A]1) OVER P N [Hp] P N [kW] [lbs.] [kg] ACS 311-1P1-1 R0 6.6 - 3.0 4.5 1/2 0.55 6.8 3.1 ACS 311-1P6-1 R0 8.9 - 4.3 6.5 1 0.75 6.8 3.1 ACS 301-2P1-1 R1 12.2 - 5.5 8.3 1-1/2 1.1 10.1 4.6 ACS 311-2P1-1 R1 12.2 8.4 5.5 8.3 1-1/2 1.1 10.1 4.6 ACS 301-2P7-1 R1 15.7 - 7.1 10.7 2 1.5 10.1 4.6 ACS 311-2P7-1 R1 15.7 9.8 7.1 10.7 2 1.5 10.1 4.6 ACS 301-4P1-1 R1 22.4 - 10.7 13.0 3 2.2 10.1 4.6 ACS 311-4P1-1 R1 22.4 12.9 10.7 13.0 3 2.2 10.1 4.6