AH500 Module Manual External wiring (1) AH06XA-5A 4-wire: Voltage input -10V~+1 0V Shielded cable 1 * CH0 AG +24V + - *3 1 M CH0 0V *6 SG AG 4-wire: C urrent input -20m A~+20m A Shielded cable CH1 +24 V 0 V + - CH1 *6 2-wire: Current input 4 mA~+20 mA SG +24V + Shielded cable 1 * CH2 1M AG - *2 V2+ I2 + 2 50 1 M CH2 0V *6 SG VI2- 3-wire: Voltage input -10V ~+10V Shielded cable 1 * AG +24V + CH3 V3 + 1M 0 V - VI3 - I3+ 250 1M CH3 3-wire: C urrent i nput SG *6 -2 0mA~+2 0mA Shielded cable 1 * CH4 AG +24V + *2 V4+ 1 M CH4 0 V SG AC motor drive , , recorder ... proportioning valve Voltage output CH0 -10V~+1 0V CH0 VO0 I O0 Shielded cable 4 * SG *6 AG A G AC motor drive , , recorder ...
proportioning valve Current output CH1 0mA~20m A CH1 A G Shielded cable 4 * SG *6 SG *7 UP 24VDC DC/DC co nverte r ZP -1 5V AG +15 V *1. Please use a shielded cable as an analog input cable, and isolate the shielded cable from other power cables. *2. If current is connected, the connection between Vn+ and In+ needs to be a short circuit. (n is in the range of 0 to 7.) *3. If ripple voltage results in interference with the wiring, please connect a 0.1~0.47 μF and 25 V capacitor. *4. Please isolate the analog output cable from other power cables. 4-18 V0+ I0 + 25 0 1M VI 0- V1+ I1 + VI1- 1 M - I 4+ VI4 - 25 0 1M *5 V O1 I O1 A G