AH500 Module Manual 1.2 Specifications 1.2.1 General Specifications 1.2.2 EMC Standards 1.2.2.1 EMI 1.2.2.2 EMS 1-4 Item Specifications Operating -20~60°C temperature Storage temperature -40~70°C 5~95% No condensation Operating humidity 5~95% No condensation Storage humidity Vibration/Shock International standards IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) resistance Work environment No corrosive gas exists.
Installation location In a control box Pollution degree 2 Port Frequency range Level (Normative) Reference standard Enclosure port 30-230 MHz 40 dB (μV/m) quasi-peak IEC 61000-6-4 (radiated) (measured at a 230-1000 MHz 47 dB (μV/m) quasi-peak distance of 10 meters) AC power port (conducted) 0.15-0.5 MHz 79 dB (μV) quasi-peak IEC 61000-6-4 66 dB (μV) average 0.5-30 MHz 73 dB (μV) quasi-peak 60 dB (μV) average Environmental Reference standard Test Test level phenomenon Electrostatic IEC 61000-4-2 Contact ±4 kV discharge Air ±8 kV Radio frequency IEC 61000-4-3 80% AM, 1 kHz sinusoidal 2.0-2.7 GHz 1 V/m electromagnetic 1.4-2.0 GHz 3 V/m field Amplitude 80-1000 MHz 10 V/m modulated Power frequency magnetic field IEC 61000-4-8 60 Hz 30 A/m 50 Hz 30 A/m