Kaiyi — 11.7.3 Status Word Diagnosis

AH500 Module Manual 11-108 Bit Status value Indication How to deal with Bit 5 0 AHRTU-DNET-5A runs -- normally. 1 AHRTU-DNET-5A is in low voltage Check if the connection between AHRTU-DNET-5A and the rack is normal and the power module works. Bit 6 Reserved -- -- Bit 7 0 AHRTU-DNET-5A runs -- normally. 1 The configuration data of the Reduce and appropriately configure hung module exceed 980 bytes. the configuration data. Bit 8 0 The first extension rack runs -- normally. 1 The first extension rack is abnormal. Check the connection of the extension rack or replace it with another one. Bit 9 0 The second extension rack runs -- normally. 1 The second extension rack is abnormal.

Check the connection of the extension rack or replace it with another one. Bit 10 0 The third extension rack runs -- normally. 1 The third extension rack is abnormal. Check the connection of the extension rack or replace it with another one. Bit 11 0 The fourth extension rack runs -- normally. 1 The fourth extension rack is abnormal. Check the connection of the extension rack or replace it with another one. Bit 12 0 The fifth extension rack runs -- normally. 1 The fifth extension rack is abnormal. Check the connection of the extension rack or replace it with another one. Bit 13 0 The sixth extension rack runs -- normally. 1 The sixth extension rack is abnormal.

Check the connection of the extension rack or replace it with another one. Bit 14 0 The seventh extension rack -- runs normally. 1 The seventh extension rack is abnormal. Check the connection of the extension rack or replace it with another one. Bit 15 Reserved -- --