Delta Electronics AH500 — 2.5.1 General Specifications

Chapter 2 Specifications and System Configuratio n Functional specifications for the digital-to-analog conversion 2-38 Analog-to-digital Current input conversion Fiducial error ±0.1% (Room temperature) (The number of input currents which are averaged is 100.) Fiducial error (Full ±0.2% temperature range) (The number of input currents which are averaged is 100.) Linearity error ±0.05% (Room temperature) Linearity error ±0.23% (Full temperature range) Hardware 16 bits resolution Input impedance 250 Ω Absolute input ±32 mA range Digital-to-analog Voltage output conversion Rated output ±10 V 0 V~10 V ±5 V 0 V~5 V 1 V~5 V range Hardware output -10.1 V~10.1 V -0.1 V~10.1 V -5.05 V~5.05 V -0.05 V~5.05 V 0.95 V~5.05 V range Fiducial error ±0.02% (Room temperature) (The number of output voltages which are averaged is 100.) Fiducial error (Full ±0.04% temperature range) (The number of output voltages which are averaged is 100.) Linearity error ±0.004% (Room temperature) Linearity error ±0.004% (Full temperature range) Hardware 16 bits resolution Permissible load 1 kΩ~2 MΩ:

±10 V and 0 V~10 V ≧500 Ω: 1 V~5 V impedance