Delta Electronics AH500 — 2.6.2 Profiles

AH500 Operation Manual Functional specifications 2.6.2 Profiles  AH04PT-5A/AH04TC-5A/AH08TC-5A 2-49 Module name AH04TC-5A AH08TC-5A Iso Iso Iso Iso Iso Weight 19 lation between a digital circuit and a ground: 500 V DC lation between an analog circuit and a ground: 500 V DC lation between an analog circuit and a digital circuit: 500 V DC lation between the 24 V DC and a ground: 500 V DC lation between analog channels: 120 V AC 0g Analog-to-digital Centigrade (°C) Fahrenheit(°F) Voltage input conversion Type J: -100°C~1,150°C Type K: -100°C~1,350°C Type R: 0°C~1,750°C Type S: 0°C~1,750°C Type T: -150°C~390°C Type E: -150°C~980°C Type N: -150°C~1,280°C Type J: -148°F~2,102°F Type K:

-148°F~2,462°F Type R: 32°F~3,182°F Type S: 32°F~3,182°F Type T: -238°F~734°F Type E: -238°F~1,796°F Type N: -238°F~2,336°F ±150 mV Rated input range Average function Range: 1~100 Self-diagnosis Disconnection detection 1 04PT 2 RUN ERROR 3 O0 I0 I0 O0 FG O1 4 I1 I1 O1 FG O2 I2 I2 O2 FG O3 I3 I3 O3 FG 5 R2/T 3D/4 -WI RE Number 1 2 3 4 5 6 7 04PT RUN ERROR O0 I0 I0 O0 FG O1 I1 I1 O1 FG 04TC RUN ERROR I0 I0 I1 I1 I2 I2 I3 I3 FG FG 08TC RUN ERROR I0 I0 I1 I1 I2 I2 I3 I3 FG FG 7 9 8 TJ,h Ke, rRm,So,cTo,Eu,pNle 6 Name I4 I4 I5 I5 I6 I6 I7 I7 FG FG 1 TJ,h Ke, rRm,So,cTo,Eu,pNle Description 1 Model name Model name of the module Operating status of the module RUN LED indica tor ON:

The module is running. OFF: The module stops running. 2 Error status of the module ERROR LED ON: A serious error occurs in the module. indicator OFF: The module is normal. Blinking: A slight error occurs in the module. 3 Removable The inputs are connected to a sensor. terminal block Arrangement of the 4 input/output Arrangement of the terminals terminals 5 Description of th e Simple specifications for the module inputs/outputs 6 Clip Removing the terminal block 7 Label Nameplate