Chapter 2 Specifications and System Configuratio n AH10DNET-5A 12 1. Address knobs It is used to set the node address of AH10DNET-5A on a DeviceNet network. (Node addresses range from 0 to 63.) Example: If users want to set the communication address of AH10DNET-5A to 26, they can turn the knob corresponding to x10 1 to 2, and turn the knob corresponding to x10 0 to 6. Points for attention: After the station address of AH10DNET-5A is changed, users have to power AH10DNET-5A again, otherwise the change will not take effect. Please use a slotted screwdriver to turn the knobs with care, and do not scrape them. 2. Function switch The function switch provides the following functions:
Setting the working mode (IN 0) Setting the transmission speed of a DeviceNet network (DR 0~DR 1) 2-60 2 3 4 5 MS 6 N S 7 x101 x100 D R 1 D R 0 IN 1 IN 0 Nod e Ad dress 9 8 11 10 Number Name Description 1 Model name Model name of the module Seven-segment 2 Display display 3 Address knob Setting the address 4 Function switch Setting the functions 5 DeviceNet connector DeviceNet is used to interconnect control devices for data exchange.
6 MS LED indicator Indicating the status of the module 7 NS LED indicator Indicating the status of the network Removable terminal 8 Terminals for wiring block 9 Label Nameplate 10 Set screw Fixing the module 11 Connector Connecting the module and a backplane. 12 Projection Fixing the module Setting Description 0…63 Available nodes on a DeviceNet network 64…99 Unavailable nodes on a DeviceNet network