Delta AH500 — 6.8.2 Explanation of Convenience Instructions

AH500 Programming Manual 6-186 Device Function Setting range Description Device number number less than the absolute value of ERR DBW, and _ check whether the present error meets the cross status condition. If the present error is less than the absolute value of ERR DBW, and _ meets the cross status condition, the present error will be count as 0, and the PID algorithm will be implemented, otherwise the present error will be brought into the PID algorithm according to the normal processing. MV MAX _ REAL Maximum output value Range of single-precision floating-point values Example: After MV MAX is set to _ 1,000, an MV will be 1,000 if it exceeds 1,000.

MV MAX has to _ be greater than MV MIN, _ otherwise the maximum output value set and the minimum output value set will be interchanged. MV MIN _ REAL Minimum output value Range of single-precision floating-point values Example: After MV MIN is set to - _ 1,000, an MV will be - 1,000 if it is less than than -1,000. MV MIN _ has to be lessthan MV MAX, _ otherwise the maximum output value set and the minimum output value set will be interchanged. MOUT REAL Manual output value Range of single-precision floating-point values Mout and PID MAN are _ used together. If PID MAN is set to _ true, the MV will be